Bicity Solar Energy Suppliers

Solis 5kW 48V Hybrid Inverter

KSh 70,000.00

  • Type: Off grid inverter, not a hybrid, with no grid export
  • Power: 5kW and 5kVA, surging to 10kVA for 10 seconds
  • Charging input: Accepts 90V to 280V, so weak supplies still work
  • Fast charge: Up to 80A from a grid connection or generator
  • Solar: 6.5kW usable on one tracker carrying two strings
  • Battery: 40V to 60V at 100A, lithium or lead acid, non communicating packs supported
  • Loads: Two backup outputs, so essentials outlast the rest
  • Weight: 13.8kg, a one person lift
  • Important: IP21, indoor mounting only, and rated to 2000m altitude
  • Site altitude and mounting checked by Bicity Solar before quotation
– +
SKU: BC-INV-SOLIS-S6EH1P5K Category: Brand:

Description

The Solis S6-EH1P5K-L-PLUS delivers 5000W from a 48V battery, and the thing worth knowing about it is not on the first line of any specification sheet.

Nothing inside it spins. It sheds heat through its own finned casing, by convection, with no fan fitted anywhere. In this series that stops being true one step up: the 3kW, 3.6kW and 5kW are cooled by air movement alone, while every model from 6kW upward carries an intelligent fan. So this is the largest fan free unit Solis builds in the range.

That matters more in Kenya than it would elsewhere. A fan is the only moving part in an inverter, which makes it the first component to wear out, and it works by pulling outside air across the electronics. Outside air here carries dust through the dry months and salt along the coast. Remove the fan and you remove the wear item, the noise and the mechanism that draws grit inside.

Three other figures shape how it behaves on a real installation.

It permits 10kW of panel against 5kW of output. Twice the array, deliberately, because a 10kW array almost never produces 10kW once heat, haze and dust have taken their share. The oversizing fills the shoulders of the day rather than chasing a midday peak.

Its 112 ampere battery rating genuinely matches its output. Reaching 5kW asks about 98 amperes from a bank sitting at 51.2V and roughly 114 at a deeply drawn down 44V. Many inverters fall short here, forcing a larger bank purely to supply current. This one does not.

It hands over to backup in under 10 milliseconds. A mains cycle lasts 20, so the gap is under half a cycle, shorter than the hold up time built into virtually any computer, till or router power supply. Equipment does not notice the supply failing.

Solis 5kW Hybrid Inverter Specifications, Cooling and Installation

1. System Architecture and Configuration

Grid Output and Backup

  • 5kW and 5kVA, single phase across live, neutral and earth
  • 220V or 230V at 50Hz or 60Hz
  • 22.8 amperes at 220V, or 21.8 at 230V
  • Power factor better than 0.99, adjustable across 0.8 either way
  • Current distortion held under 3% on the grid side
  • Backup rated at the same 5kW, doubling for ten seconds
  • Handover to backup inside 10 milliseconds
  • Backup voltage distortion under 2% on a linear load
  • Up to 40 amperes able to pass through to the backup circuit
  • A reserve level you set, below which the battery is held for outages

Solar Input

  • Two independent trackers, one string on each
  • 10kW of array permitted, 8kW of that converted at any moment
  • Ceiling of 500V, nominal 330V, tracking across 90V to 435V
  • Generation beginning from 90V
  • Sixteen amperes per tracker, twenty amperes of short circuit current
  • Solar alone able to run the backup circuit, with no battery contribution
  • An existing grid tied array able to feed in, with export under control

Battery and Charging

  • Lithium or lead acid, any bank between 40V and 60V
  • 5kW of charging and 5kW of discharging
  • One hundred and twelve amperes in either direction
  • CAN or RS485 for battery communication
  • Six periods you can programme across the day
  • The battery side galvanically isolated from the rest

Protection and Cooling

  • Heat shed by convection alone, nothing fitted that turns
  • Anti islanding, so it disconnects when the grid goes down
  • Ground fault monitoring and reverse polarity protection on the DC side
  • Arc fault detection obtainable as an extra
  • Category III surge classification where the AC side connects
  • IP66, which allows an exterior wall

2. Technical Specifications

Parameter Value
Recommended maximum array size 10kW
Maximum usable solar input 8kW
Maximum input voltage 500V
Rated input voltage 330V
Start-up voltage 90V
Tracking window 90V to 435V
Maximum input current 16A on each tracker
Maximum short circuit current 20A on each tracker
Trackers and strings 2 trackers, 2 strings
Battery type Lithium ion or lead acid
Battery voltage range 40V to 60V
Maximum charge and discharge power 5kW
Maximum charge and discharge current 112A
Battery communication CAN or RS485
Rated output power 5kW
Maximum apparent output power 5kVA
Operation phase Live, neutral and earth
Rated output voltage 220V or 230V
Rated frequency 50Hz or 60Hz
Rated output current 22.8A at 220V, 21.8A at 230V
Power factor Above 0.99, adjustable 0.8 leading to 0.8 lagging
Current distortion Under 3%
Grid input voltage range 187V to 253V
Grid maximum input current 32A
Grid frequency range 45Hz to 55Hz, or 55Hz to 65Hz
Backup rated output power 5kW
Backup overload Twice rated power for 10 seconds
Backup switch time Under 10ms
Maximum AC passthrough current 40A
Backup voltage distortion at linear load Under 2%
Generator maximum input power 5kW
Generator maximum input current 22.8A at 220V, 21.8A at 230V
Maximum efficiency 96.2%
European weighted efficiency 96.1%
Battery charged from solar, maximum efficiency 95.3%
Battery charged from AC, maximum efficiency 93.9%
Battery discharged to AC, maximum efficiency 93.8%
Anti islanding protection Yes
Ground fault monitoring Yes
DC reverse polarity protection Yes
Integrated arc fault detection Optional
Protection class and overvoltage category Class I, category II on solar and battery, category III on mains, backup and generator
Dimensions 335 x 560 x 253mm
Weight 23kg
Topology High frequency, with isolation on the battery side
Cooling Natural convection, no fan
Noise emission, typical Under 65 dB(A)
Operating temperature -25C to +60C
Relative humidity 0% to 100%
Protection rating IP66
Maximum altitude 3000m
Parallel capability 6 units, giving 30kW
Solar connection MC4 plugs
Battery and AC connection Terminal blocks
Display 7.0 inch LCD, with Bluetooth and app
Communication RS485 and CAN, with WiFi, GPRS or LAN available
Safety and compatibility standards IEC and EN 62109, EN 61000, IEC 62116, IEC 61727, EN 50549-1, G98, G99, NRS 097-2-1

3. Key Features

  • The largest model in its series with no fan fitted, cooled entirely by convection
  • Twice the array against the output, with 8kW converted from 10kW installed
  • Tracking that begins at 90V, catching the first weak hour after sunrise
  • A battery current ceiling that holds full output almost throughout discharge
  • Handover to backup in under half a mains cycle
  • Double output for ten seconds, which starts pumps and compressors
  • Solar able to carry the backup circuit on its own, with no battery drawn on
  • A reserve level you choose, keeping charge aside for outages
  • Load prioritising, so the important circuits outlast the rest
  • A generator port of its own, with automatic control
  • Seven inches of screen, the largest in the range
  • Galvanic isolation on the battery side
  • Six units able to run together for 30kW
  • Mounting position assessed by Bicity Solar before quotation

4. Applications and Use Cases

  • Homes where quiet matters: a corridor, landing or bedroom wall, with nothing audible
  • Dusty inland sites: no fan means no air deliberately drawn across the electronics
  • Coastal installations: salt laden air is not pulled through the casing
  • Clinics and surgeries: the handover is quicker than equipment can detect
  • Shops, salons and offices: tills, routers and card machines ride through outages
  • Boreholes and pressure pumps: the ten second overload covers motor starting
  • Phased installations: panels and inverter first, battery added afterwards
  • Premises on a sagging feeder: the grid window reaches down to 187V

5. Installation and Engineering Notes

A fan free inverter has to be sited properly

Convection cooling is an advantage that depends entirely on the mounting position, because the casing can only shed heat into air that is free to move. Fitted correctly it will outlast a fan cooled unit. Fitted into a sealed cupboard it will throttle back on a hot afternoon, which is the one way to turn the strength into a weakness.

  • Leave the casing clear above and below, so warm air can rise away from it
  • Mount it vertically, which is the orientation convection depends on
  • Avoid an unventilated cupboard, a boxed meter cabinet or a sealed riser
  • Keep it off a wall in direct afternoon sun, despite the IP66 rating
  • Do not stack anything against the fins or hang bags from the bracket

The three AC currents that get confused

This unit publishes three different AC figures and they are routinely conflated, which leads to an undersized backup board.

Which current Figure What it governs
Inverter output 22.8A What the unit itself can produce
Grid input 32A What it can draw in to charge and supply
Backup passthrough 40A What can flow to the backup circuit with the grid present

The backup distribution board is sized on the 40 ampere figure, not the 22.8. With the grid up, the inverter passes supply straight through, and that path carries more than the inverter alone produces.

Circuit sizing

Devices sit a quarter above the continuous current on each circuit, then round up to a size that is actually manufactured. Measured runs, grouping and ambient heat move the final answer.

Circuit Design current Device Cable, short run
Solar, each string 20A 25A DC, rated beyond 500V 4mm² solar cable
Battery 112A 150A DC 50mm²
Grid input 32A 40A, 2 pole 10mm²
Backup board 40A 50A, 2 pole 10mm²
Generator input 22.8A 32A, 2 pole 6mm²

String design

Two trackers take one string each. The tracking window opens at 90V, which is about three modules, but opening the window is not the same as filling the inverter. Converting the full 8kW across 32 amperes of tracker capacity needs roughly 250V, so a string has to reach that before full output is even arithmetically available.

Modules at 620W Working voltage Cold dawn, open circuit Two strings Verdict
4 Around 168V Around 220V 4,960W Runs, but under the full load threshold
6 Around 252V Around 330V 7,440W Clears the threshold, a sound choice
8 Around 336V Around 440V 9,920W The configuration we usually specify
9 Around 378V Around 495V 11,160W At the voltage ceiling, verify module figures
10 Around 420V Over 500V 12,400W Exceeds the limit on a cold morning
  • Two strings of eight modules comes nearest the 10kW allowance
  • A 620W module draws roughly 14.8 amperes against a 16 ampere tracker limit
  • That leaves no room to parallel a second string onto one tracker
  • Two trackers means the two strings may face different directions
  • DC protection must carry a rating beyond 500V
  • Battery cable at 112 amperes wants crimped lugs and torqued terminals
  • Where a generator is used, wire its control signal during installation
  • Commissioning and certification handled by licensed staff

6. Care, Maintenance and Operations

  • Brush dust off the fins, since convection depends on the casing being clear
  • Confirm nothing has been stored against it or stacked underneath
  • Retighten battery terminals yearly at 112 amperes
  • Check the reserve level still matches how often outages happen
  • Review which circuits sit on the backup board as the household changes
  • Rinse the array when the dusty season breaks
  • Watch the recorded figures for a slow decline, which usually means soiling
  • On lead acid, check electrolyte and charge settings at every visit

7. Do’s and Don’ts

Do

  • Mount it upright with clear air above and below the casing
  • Size the array toward the 10kW allowance rather than the 5kW output
  • Reach at least six modules a string if full output matters
  • Size the backup board on 40 amperes of passthrough
  • Set a reserve level that reflects local outage frequency
  • Take advantage of two trackers where the roof faces two ways
  • Choose a bank that genuinely sustains 112 amperes

Don’t

  • Shut it inside an unventilated cupboard or a sealed meter box
  • Mount it flat or at an angle, since convection needs it vertical
  • Size the backup board on the 22.8 ampere output figure
  • Parallel a second string onto one tracker, as the current limit forbids it
  • Build a string of ten modules at 620W, which passes 500V when cold
  • Assume quiet running survives a cramped installation position

8. Compatibility

  • Lithium or lead acid banks anywhere between 40V and 60V
  • Packs communicating over CAN or RS485
  • Arrays to 10kW installed, on two strings that may face differently
  • An existing grid tied array, feeding in with export kept under control
  • Generators on a dedicated port, started and stopped automatically
  • Grid supply anywhere from 187V to 253V
  • Up to six units together, reaching 30kW
  • Monitoring by Bluetooth and app, with WiFi, GPRS or LAN available

Because solar alone can carry the backup circuit, a system can be commissioned and earning its keep before the battery is bought, with the battery added later without replacing anything. The exact configuration for running without storage is set at commissioning.

9. Performance Table

What array size actually buys, on a conservative Kenyan yield.

Array installed Ratio to output Typical daily generation What happens in practice
5kW 1 to 1 Around 21kWh The inverter sits idle most of the day
7.5kW 1.5 to 1 Around 31kWh A balanced choice, no capacity wasted
10kW 2 to 1 Around 40kWh Fills the morning and evening shoulders, trims briefly at noon

Worked at roughly 4.2kWh per installed kilowatt per day, which allows for heat, dust and haze rather than quoting test conditions. Cloud, orientation and soiling move every line. The 10kW column loses a little to trimming around midday and gains considerably more at both ends of the day, which is the whole reason for oversizing.

10. Where It Sits in the Series

This model belongs to a family running from 3kW to 10kW, and there is one boundary inside that family worth understanding before choosing.

Model Cooling Array permitted Battery current
3kW Convection, no fan 6kW 70A
3.6kW Convection, no fan 7.2kW 80A
5kW, this model Convection, no fan 10kW 112A
6kW Fan assisted 12kW 135A
8kW Fan assisted 16kW 190A
9kW Fan assisted 18kW 200A
10kW Fan assisted 20kW 210A

The fan appears at 6kW, which makes this the largest unit in the series with no moving part inside it. If silence or dust is the priority, going one step up in power means accepting a fan. If the load genuinely needs more than 5kW, that trade is worth making, and the larger models are well built. The point is to make the trade knowingly rather than discover it after installation.

There is also a 5kW off grid model in the Solis range at the same output. It is a different machine: indoor rated, limited to a lower altitude, with a single tracker. Anyone comparing the two at 5kW should look at both, because the right answer depends on whether a usable grid connection exists.

11. Mini FAQ

Does it have a fan?
No. It cools by convection through its own casing, and it is the largest model in the series built that way.

How fast does backup take over?
Under 10 milliseconds, which is less than half a mains cycle and quicker than equipment power supplies can register.

How much panel can I fit?
Ten kilowatts installed, of which eight is converted at any instant. Size toward the 10kW figure.

Can it go outside?
Yes, it is IP66 rated. Keep it off a wall that takes direct afternoon sun, and leave air free to move around it.

Can I start without a battery?
Yes. Solar alone can carry the backup circuit, so the battery can follow later without replacing anything.

Will a single battery support full output?
A 51.2V pack rated near 100 amperes continuous comes close, and two in parallel clear it comfortably.

What size breaker does the backup board need?
Forty amperes of passthrough, not the 22.8 ampere output figure, because the grid passes straight through when it is up.

Can my roof face two directions?
Yes. There are two independent trackers, so the two strings need not match.

12. Why Buy From Bicity Solar

  • Mounting position assessed for convection, since this unit has no fan to rely on
  • Array sized toward the 10kW allowance instead of the output figure
  • Strings built to clear the full load threshold, not merely to start the tracker
  • Backup board sized on passthrough current, which is where corners get cut
  • Reserve level and load priorities configured rather than left on defaults
  • Honest comparison against the fan cooled models and the off grid alternative
  • Hardware supplied with documentation that matches the serial number
  • Work carried out under a valid EPRA licence and signed off
  • Any warranty dispute handled by us with the distributor directly
  • Delivery to any county, with parts and help available afterwards

If you want a 5kW hybrid with nothing moving inside it, this is the one, and it is the largest in its series built that way. Tell us where it would hang and we will tell you honestly whether that position suits a fan free unit.

Send us the loads you run, the roof you have and the position you had in mind. We size the array toward the allowance, build the strings to clear full output, and specify the backup board on the right current. The Solar Calculator lets you work the loads yourself; My Quote gets it costed.

Need Help? Chat with us!
Start a Conversation
Hi! Click one of our members below to chat on WhatsApp
We usually reply in a few minutes