Description
The Solis S6-EH1P5K-L-PLUS delivers 5000W from a 48V battery, and the thing worth knowing about it is not on the first line of any specification sheet.
Nothing inside it spins. It sheds heat through its own finned casing, by convection, with no fan fitted anywhere. In this series that stops being true one step up: the 3kW, 3.6kW and 5kW are cooled by air movement alone, while every model from 6kW upward carries an intelligent fan. So this is the largest fan free unit Solis builds in the range.
That matters more in Kenya than it would elsewhere. A fan is the only moving part in an inverter, which makes it the first component to wear out, and it works by pulling outside air across the electronics. Outside air here carries dust through the dry months and salt along the coast. Remove the fan and you remove the wear item, the noise and the mechanism that draws grit inside.
Three other figures shape how it behaves on a real installation.
It permits 10kW of panel against 5kW of output. Twice the array, deliberately, because a 10kW array almost never produces 10kW once heat, haze and dust have taken their share. The oversizing fills the shoulders of the day rather than chasing a midday peak.
Its 112 ampere battery rating genuinely matches its output. Reaching 5kW asks about 98 amperes from a bank sitting at 51.2V and roughly 114 at a deeply drawn down 44V. Many inverters fall short here, forcing a larger bank purely to supply current. This one does not.
It hands over to backup in under 10 milliseconds. A mains cycle lasts 20, so the gap is under half a cycle, shorter than the hold up time built into virtually any computer, till or router power supply. Equipment does not notice the supply failing.
Solis 5kW Hybrid Inverter Specifications, Cooling and Installation
1. System Architecture and Configuration
Grid Output and Backup
- 5kW and 5kVA, single phase across live, neutral and earth
- 220V or 230V at 50Hz or 60Hz
- 22.8 amperes at 220V, or 21.8 at 230V
- Power factor better than 0.99, adjustable across 0.8 either way
- Current distortion held under 3% on the grid side
- Backup rated at the same 5kW, doubling for ten seconds
- Handover to backup inside 10 milliseconds
- Backup voltage distortion under 2% on a linear load
- Up to 40 amperes able to pass through to the backup circuit
- A reserve level you set, below which the battery is held for outages
Solar Input
- Two independent trackers, one string on each
- 10kW of array permitted, 8kW of that converted at any moment
- Ceiling of 500V, nominal 330V, tracking across 90V to 435V
- Generation beginning from 90V
- Sixteen amperes per tracker, twenty amperes of short circuit current
- Solar alone able to run the backup circuit, with no battery contribution
- An existing grid tied array able to feed in, with export under control
Battery and Charging
- Lithium or lead acid, any bank between 40V and 60V
- 5kW of charging and 5kW of discharging
- One hundred and twelve amperes in either direction
- CAN or RS485 for battery communication
- Six periods you can programme across the day
- The battery side galvanically isolated from the rest
Protection and Cooling
- Heat shed by convection alone, nothing fitted that turns
- Anti islanding, so it disconnects when the grid goes down
- Ground fault monitoring and reverse polarity protection on the DC side
- Arc fault detection obtainable as an extra
- Category III surge classification where the AC side connects
- IP66, which allows an exterior wall
2. Technical Specifications
| Parameter | Value |
|---|---|
| Recommended maximum array size | 10kW |
| Maximum usable solar input | 8kW |
| Maximum input voltage | 500V |
| Rated input voltage | 330V |
| Start-up voltage | 90V |
| Tracking window | 90V to 435V |
| Maximum input current | 16A on each tracker |
| Maximum short circuit current | 20A on each tracker |
| Trackers and strings | 2 trackers, 2 strings |
| Battery type | Lithium ion or lead acid |
| Battery voltage range | 40V to 60V |
| Maximum charge and discharge power | 5kW |
| Maximum charge and discharge current | 112A |
| Battery communication | CAN or RS485 |
| Rated output power | 5kW |
| Maximum apparent output power | 5kVA |
| Operation phase | Live, neutral and earth |
| Rated output voltage | 220V or 230V |
| Rated frequency | 50Hz or 60Hz |
| Rated output current | 22.8A at 220V, 21.8A at 230V |
| Power factor | Above 0.99, adjustable 0.8 leading to 0.8 lagging |
| Current distortion | Under 3% |
| Grid input voltage range | 187V to 253V |
| Grid maximum input current | 32A |
| Grid frequency range | 45Hz to 55Hz, or 55Hz to 65Hz |
| Backup rated output power | 5kW |
| Backup overload | Twice rated power for 10 seconds |
| Backup switch time | Under 10ms |
| Maximum AC passthrough current | 40A |
| Backup voltage distortion at linear load | Under 2% |
| Generator maximum input power | 5kW |
| Generator maximum input current | 22.8A at 220V, 21.8A at 230V |
| Maximum efficiency | 96.2% |
| European weighted efficiency | 96.1% |
| Battery charged from solar, maximum efficiency | 95.3% |
| Battery charged from AC, maximum efficiency | 93.9% |
| Battery discharged to AC, maximum efficiency | 93.8% |
| Anti islanding protection | Yes |
| Ground fault monitoring | Yes |
| DC reverse polarity protection | Yes |
| Integrated arc fault detection | Optional |
| Protection class and overvoltage category | Class I, category II on solar and battery, category III on mains, backup and generator |
| Dimensions | 335 x 560 x 253mm |
| Weight | 23kg |
| Topology | High frequency, with isolation on the battery side |
| Cooling | Natural convection, no fan |
| Noise emission, typical | Under 65 dB(A) |
| Operating temperature | -25C to +60C |
| Relative humidity | 0% to 100% |
| Protection rating | IP66 |
| Maximum altitude | 3000m |
| Parallel capability | 6 units, giving 30kW |
| Solar connection | MC4 plugs |
| Battery and AC connection | Terminal blocks |
| Display | 7.0 inch LCD, with Bluetooth and app |
| Communication | RS485 and CAN, with WiFi, GPRS or LAN available |
| Safety and compatibility standards | IEC and EN 62109, EN 61000, IEC 62116, IEC 61727, EN 50549-1, G98, G99, NRS 097-2-1 |
3. Key Features
- The largest model in its series with no fan fitted, cooled entirely by convection
- Twice the array against the output, with 8kW converted from 10kW installed
- Tracking that begins at 90V, catching the first weak hour after sunrise
- A battery current ceiling that holds full output almost throughout discharge
- Handover to backup in under half a mains cycle
- Double output for ten seconds, which starts pumps and compressors
- Solar able to carry the backup circuit on its own, with no battery drawn on
- A reserve level you choose, keeping charge aside for outages
- Load prioritising, so the important circuits outlast the rest
- A generator port of its own, with automatic control
- Seven inches of screen, the largest in the range
- Galvanic isolation on the battery side
- Six units able to run together for 30kW
- Mounting position assessed by Bicity Solar before quotation
4. Applications and Use Cases
- Homes where quiet matters: a corridor, landing or bedroom wall, with nothing audible
- Dusty inland sites: no fan means no air deliberately drawn across the electronics
- Coastal installations: salt laden air is not pulled through the casing
- Clinics and surgeries: the handover is quicker than equipment can detect
- Shops, salons and offices: tills, routers and card machines ride through outages
- Boreholes and pressure pumps: the ten second overload covers motor starting
- Phased installations: panels and inverter first, battery added afterwards
- Premises on a sagging feeder: the grid window reaches down to 187V
5. Installation and Engineering Notes
A fan free inverter has to be sited properly
Convection cooling is an advantage that depends entirely on the mounting position, because the casing can only shed heat into air that is free to move. Fitted correctly it will outlast a fan cooled unit. Fitted into a sealed cupboard it will throttle back on a hot afternoon, which is the one way to turn the strength into a weakness.
- Leave the casing clear above and below, so warm air can rise away from it
- Mount it vertically, which is the orientation convection depends on
- Avoid an unventilated cupboard, a boxed meter cabinet or a sealed riser
- Keep it off a wall in direct afternoon sun, despite the IP66 rating
- Do not stack anything against the fins or hang bags from the bracket
The three AC currents that get confused
This unit publishes three different AC figures and they are routinely conflated, which leads to an undersized backup board.
| Which current | Figure | What it governs |
|---|---|---|
| Inverter output | 22.8A | What the unit itself can produce |
| Grid input | 32A | What it can draw in to charge and supply |
| Backup passthrough | 40A | What can flow to the backup circuit with the grid present |
The backup distribution board is sized on the 40 ampere figure, not the 22.8. With the grid up, the inverter passes supply straight through, and that path carries more than the inverter alone produces.
Circuit sizing
Devices sit a quarter above the continuous current on each circuit, then round up to a size that is actually manufactured. Measured runs, grouping and ambient heat move the final answer.
| Circuit | Design current | Device | Cable, short run |
|---|---|---|---|
| Solar, each string | 20A | 25A DC, rated beyond 500V | 4mm² solar cable |
| Battery | 112A | 150A DC | 50mm² |
| Grid input | 32A | 40A, 2 pole | 10mm² |
| Backup board | 40A | 50A, 2 pole | 10mm² |
| Generator input | 22.8A | 32A, 2 pole | 6mm² |
String design
Two trackers take one string each. The tracking window opens at 90V, which is about three modules, but opening the window is not the same as filling the inverter. Converting the full 8kW across 32 amperes of tracker capacity needs roughly 250V, so a string has to reach that before full output is even arithmetically available.
| Modules at 620W | Working voltage | Cold dawn, open circuit | Two strings | Verdict |
|---|---|---|---|---|
| 4 | Around 168V | Around 220V | 4,960W | Runs, but under the full load threshold |
| 6 | Around 252V | Around 330V | 7,440W | Clears the threshold, a sound choice |
| 8 | Around 336V | Around 440V | 9,920W | The configuration we usually specify |
| 9 | Around 378V | Around 495V | 11,160W | At the voltage ceiling, verify module figures |
| 10 | Around 420V | Over 500V | 12,400W | Exceeds the limit on a cold morning |
- Two strings of eight modules comes nearest the 10kW allowance
- A 620W module draws roughly 14.8 amperes against a 16 ampere tracker limit
- That leaves no room to parallel a second string onto one tracker
- Two trackers means the two strings may face different directions
- DC protection must carry a rating beyond 500V
- Battery cable at 112 amperes wants crimped lugs and torqued terminals
- Where a generator is used, wire its control signal during installation
- Commissioning and certification handled by licensed staff
6. Care, Maintenance and Operations
- Brush dust off the fins, since convection depends on the casing being clear
- Confirm nothing has been stored against it or stacked underneath
- Retighten battery terminals yearly at 112 amperes
- Check the reserve level still matches how often outages happen
- Review which circuits sit on the backup board as the household changes
- Rinse the array when the dusty season breaks
- Watch the recorded figures for a slow decline, which usually means soiling
- On lead acid, check electrolyte and charge settings at every visit
7. Do’s and Don’ts
Do
- Mount it upright with clear air above and below the casing
- Size the array toward the 10kW allowance rather than the 5kW output
- Reach at least six modules a string if full output matters
- Size the backup board on 40 amperes of passthrough
- Set a reserve level that reflects local outage frequency
- Take advantage of two trackers where the roof faces two ways
- Choose a bank that genuinely sustains 112 amperes
Don’t
- Shut it inside an unventilated cupboard or a sealed meter box
- Mount it flat or at an angle, since convection needs it vertical
- Size the backup board on the 22.8 ampere output figure
- Parallel a second string onto one tracker, as the current limit forbids it
- Build a string of ten modules at 620W, which passes 500V when cold
- Assume quiet running survives a cramped installation position
8. Compatibility
- Lithium or lead acid banks anywhere between 40V and 60V
- Packs communicating over CAN or RS485
- Arrays to 10kW installed, on two strings that may face differently
- An existing grid tied array, feeding in with export kept under control
- Generators on a dedicated port, started and stopped automatically
- Grid supply anywhere from 187V to 253V
- Up to six units together, reaching 30kW
- Monitoring by Bluetooth and app, with WiFi, GPRS or LAN available
Because solar alone can carry the backup circuit, a system can be commissioned and earning its keep before the battery is bought, with the battery added later without replacing anything. The exact configuration for running without storage is set at commissioning.
9. Performance Table
What array size actually buys, on a conservative Kenyan yield.
| Array installed | Ratio to output | Typical daily generation | What happens in practice |
|---|---|---|---|
| 5kW | 1 to 1 | Around 21kWh | The inverter sits idle most of the day |
| 7.5kW | 1.5 to 1 | Around 31kWh | A balanced choice, no capacity wasted |
| 10kW | 2 to 1 | Around 40kWh | Fills the morning and evening shoulders, trims briefly at noon |
Worked at roughly 4.2kWh per installed kilowatt per day, which allows for heat, dust and haze rather than quoting test conditions. Cloud, orientation and soiling move every line. The 10kW column loses a little to trimming around midday and gains considerably more at both ends of the day, which is the whole reason for oversizing.
10. Where It Sits in the Series
This model belongs to a family running from 3kW to 10kW, and there is one boundary inside that family worth understanding before choosing.
| Model | Cooling | Array permitted | Battery current |
|---|---|---|---|
| 3kW | Convection, no fan | 6kW | 70A |
| 3.6kW | Convection, no fan | 7.2kW | 80A |
| 5kW, this model | Convection, no fan | 10kW | 112A |
| 6kW | Fan assisted | 12kW | 135A |
| 8kW | Fan assisted | 16kW | 190A |
| 9kW | Fan assisted | 18kW | 200A |
| 10kW | Fan assisted | 20kW | 210A |
The fan appears at 6kW, which makes this the largest unit in the series with no moving part inside it. If silence or dust is the priority, going one step up in power means accepting a fan. If the load genuinely needs more than 5kW, that trade is worth making, and the larger models are well built. The point is to make the trade knowingly rather than discover it after installation.
There is also a 5kW off grid model in the Solis range at the same output. It is a different machine: indoor rated, limited to a lower altitude, with a single tracker. Anyone comparing the two at 5kW should look at both, because the right answer depends on whether a usable grid connection exists.
11. Mini FAQ
Does it have a fan?
No. It cools by convection through its own casing, and it is the largest model in the series built that way.
How fast does backup take over?
Under 10 milliseconds, which is less than half a mains cycle and quicker than equipment power supplies can register.
How much panel can I fit?
Ten kilowatts installed, of which eight is converted at any instant. Size toward the 10kW figure.
Can it go outside?
Yes, it is IP66 rated. Keep it off a wall that takes direct afternoon sun, and leave air free to move around it.
Can I start without a battery?
Yes. Solar alone can carry the backup circuit, so the battery can follow later without replacing anything.
Will a single battery support full output?
A 51.2V pack rated near 100 amperes continuous comes close, and two in parallel clear it comfortably.
What size breaker does the backup board need?
Forty amperes of passthrough, not the 22.8 ampere output figure, because the grid passes straight through when it is up.
Can my roof face two directions?
Yes. There are two independent trackers, so the two strings need not match.
12. Why Buy From Bicity Solar
- Mounting position assessed for convection, since this unit has no fan to rely on
- Array sized toward the 10kW allowance instead of the output figure
- Strings built to clear the full load threshold, not merely to start the tracker
- Backup board sized on passthrough current, which is where corners get cut
- Reserve level and load priorities configured rather than left on defaults
- Honest comparison against the fan cooled models and the off grid alternative
- Hardware supplied with documentation that matches the serial number
- Work carried out under a valid EPRA licence and signed off
- Any warranty dispute handled by us with the distributor directly
- Delivery to any county, with parts and help available afterwards
If you want a 5kW hybrid with nothing moving inside it, this is the one, and it is the largest in its series built that way. Tell us where it would hang and we will tell you honestly whether that position suits a fan free unit.
Send us the loads you run, the roof you have and the position you had in mind. We size the array toward the allowance, build the strings to clear full output, and specify the backup board on the right current. The Solar Calculator lets you work the loads yourself; My Quote gets it costed.



